Class-A compliance for the most demanding power quality tests
The Fluke 1760 Three-Phase Power Quality Recorder is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. Designed for analysis of utility and industrial power distribution systems, in medium- and low-voltage networks, this power quality monitor provides the flexibility to customize thresholds, algorithms, and measurement selections. The 1760 power recorder captures the most comprehensive details on user-selected parameters.
Applications
Detailed disturbance analysis – Perform high-speed transient analysis and uncover root cause of equipment malfunction for later mitigation and predictive maintenance. The fast transient option, with its 6000 V measurement range, allows capture of very short impulses such as lightning strikes.
Class-A quality-of-service compliance – Validate incoming power quality at the service entrance. Thanks to Class A compliance, the Fluke 1760 allows undisputable verification.
Event correlation at multiple locations – Utilizing GPS time synchronization, users can quickly detect where a fault occurred first, either inside or outside the facility.
Galvanic separation and DC coupling – Allows complete measurements on dissimilar power systems. For example troubleshoot UPS systems by simultaneously recording the battery voltage and power output.
Power quality and power load studies – Assess baseline power quality to validate compatibility with critical systems before installation and verify electrical system capacity before adding loads.
There are four Fluke 1760 models to select from:
| Product Feature | Fluke 1760 Basic | Fluke 1760TR Basic | Fluke 1760 | Fluke 1760TR |
| Power quality statistics according to EN50160 | ● | ● | ● | ● |
| Voltage event list (dips, swells and interruptions) | ● | ● | ● | ● |
| Continuous recording of: | ||||
| Voltage | ● | ● | ● | ● |
| Current | ● | ● | ● | ● |
| Power P, Q, S | ● | ● | ● | ● |
| Power factor | ● | ● | ● | ● |
| kWh | ● | ● | ● | ● |
| Flicker | ● | ● | ● | ● |
| Unbalance | ● | ● | ● | ● |
| Frequency | ● | ● | ● | ● |
| Voltage and current harmonics to the 50th / Interharmonics | ● | ● | ● | ● |
| THD | ● | ● | ● | ● |
| Mains signaling | ● | ● | ● | ● |
| Triggered recordings | ● | ● | ● | ● |
| Online mode (Oscilloscope, transients and events) | ● | ● | ● | ● |
| Fast transient analysis up to 10 MHz | ● | ● | ||
| 4, 600V voltage probes | ● | ● | ||
| 4 dual-range flexible current probes (1000 A / 200 A ac) | ● | ● | ||
| GPS time sync receiver | ● | ● | ||
| Memory | 2 GB Flash memory | |||